Chapter # 4                                                                                        PROCESSES
                                                                        Busbar Jointing

4.3   Jointing


          There are different methods of jointing of current-carrying conductors in Busbar Systems.  The most commonly used method in the order of usage is welding, bolting, and clamping.  Riveting & brazing have almost become obsolete with the advancement in welding technology.  In an enclosed bus system, it is suggested that wherever it is possible to make a welded joint, it should be opted for, since each bolted or clamped joint, apart from being expensive, would require access for maintenance.  (Welding of an Aluminium conductor is far easier than welding of a Copper conductor.)  


          A busbar joint is efficient if the resistance across it is less than or equal to the resistance of an equivalent length of the busbar, without the joint.  (In isolated phase bus, one of the methods of establishing these criteria is to compare the voltage drop across a welded section and a non-welded section of equal length, with an injected current of approximately 1000 A.  This is done for both conductor and enclosure.)


          In an isolated phase bus, the most common method of jointing of the enclosure as well as the conductor is by welding.  Bolting is resorted to only at the termination ends.  In the non-segregated and segregated phase bus, the method of jointing conductors of adjacent sections and termination is by bolting.  In the sandwich bus, the method of jointing conductors of adjacent sections is by clamping while bolting is carried out at terminating ends.


          Outdoor switchyards use tubular conductors.  Welding and clamping are extensively employed.  The welded area must be dressed to ensure that it does not contribute to corona discharge.  Many, outdoor equipment, have Copper terminals and may be required to form connections to an Aluminium busbar.  Bolting and clamping can form an effective Copper to Aluminium, joint. 


          Clamps are also used for holding the parallel conductors of the same phase.  This is different from the clamps used for current transfer and act as current equalizers.  Such clamps are necessary to limit the stresses and deflections between the conductors of the same phase during short circuit forces.  Such clamps are also used on bundled conductors in transmission lines and are referred to as spacers. 



4.3.1   Welding

          Welding is the most efficient and preferred form of jointing of Copper or Aluminium conductors.  It is permanent, does not deteriorate with time, requires no maintenance, and is extremely economical.  However, welding of Copper or Aluminium needs expertise and specific infrastructure.  Repetitive welding at works can be undertaken by robots.  Welding at the site is mostly manual and requires skilled operators.


4.3.2  Bolting

          Where it is not possible to carry out welding, bolting is the next preferred method of busbar jointing.  These joints have been in the industry, giving satisfactory performances, in onerous service conditions, for a sufficient length of time to give confidence to engineers.  An efficient joint must have a low contact resistance, maintain its integrity during its life of the joint by containing the effects of corrosion, fretting, thermal cycling, differential expansion, vibration, and fatigue.

          The joint resistance Rj can be split into two components  

Rj = Rs + Ri

          Where Rs is the resistance to the diversion of current flow (from ideal streamlined flow) through the joint and Ri is the resistance at the interface.



4.3.2.1   Resistance due to Streamline Effect – Spreading Resistance (Rs)


It has been established theoretically and observed practically that in an overlap, the current density is maximum at either end of the joint.  Consider two bars of similar dimensions having a width w and thickness t overlapping to a distance of L.  Let  be the resistance of one bar for a length L.    


Joint Resistance (Figure – 4.9)


          The graph above details the streamline effect on the joint.  It is not difficult to conclude that the value will reach 0.5 asymptotically at either end.  Increasing the length of overlap beyond a certain ratio does not yield any significant benefit in terms of reduction in streamline resistance.



4.3.2.2   Interface Resistance (Ri)


          The interface resistance depends upon the condition of the mating surface, the effective area of contact, and the pressure.


          The mating surfaces need to be flat.  It is obvious that any surface, however flat it may be machined, will have peaks and valleys when observed under a microscope.  A bar that is cast needs to be machined while a bar that is drawn or extruded need not be subjected to any further surface finishing.  The mating surfaces must have a uniform gap.  When the width of the bar is large and the surface hard, it may be necessary to cut grooves along the length of the bar up to the length of the overlap, to ensure that mating surfaces are parallel. 


          When a bolted joint is made, most of the current flows in the area below the washer.  It has been observed that interface resistance decreases with an increase in the effective contact area and applied pressure.  It is quite obvious that the pressure under the area of the washer will be more than the average pressure under the overlap.  It is, therefore, evident that the pressure should not be increased beyond the elastic value of the metal. 


          If the metal creeps, it is quite possible that it will develop hot spots during thermal cycling.  Due to the difference in the coefficient of linear expansion between the Steel fixings and the busbar (Copper or Aluminium), the contact pressure will increase with the increase in temperature.  It is, therefore, recommended to use the Belleville washers to limit and maintain the pressure on the mating surface at a safe value, at ambient temperature.  Softer conditions of alloy materials are more susceptible to joint deterioration.    


          Every hole punched or drilled to accommodate a bolt, reduces the overlap area.  Therefore, for every bolted joint, there should be an optimum bolting schedule (number of bolts, size, and pattern) that would provide the most optimal solution.


          It is necessary to ensure that the mating surfaces remain in prime condition for the rest of their life.  Aluminium and Copper will oxidize, when exposed to the atmosphere, at different rates.  These will deteriorate the parent metal and increase the joint resistance.  To prevent oxidation, it is recommended to apply a thin layer of petroleum jelly or a suitable compound. A compound with a higher softening temperature is preferable as it will not change its state when the busbars operate at high temperatures.


For Copper busbars, the joint resistance will also depend upon the hardness


For Aluminium busbars, the joint resistance will depend upon the alloy composition and temper.  Aluminium, with a conductivity of 61% (grade 1350) is soft and susceptible to creep.

 



                                             Interphase Resistance between Copper Busbars                                                
                        (Figure – 4.10) Courtesy: Copper Alliance

  

          

Interphase resistance between Busbars with Increasing and Decreasing pressure

(Figure - 4.11)


          (The graphical representations in Figures  4.10 and 4.11 are indicative.)



4.3.2.3   Fretting Resistance (Rf)


          A phenomenon of surface damage at the interface of a joint, subject to vibration and relative movement, is called fretting.  It is established that a vibration that causes a movement of 100 nanometers relative movement, can result in fretting.


          The relative movement of busbars at the joint can occur due to thermal expansion/contraction due to load and ambient temperature variations.


          It is understood that the contact resistance can be neglected if the film layer is less than 0.1 micron.  The electrons can cover this distance without loss of energy by tunneling.  If the layer is thick, the electrons lose energy and offer resistance to current flow.  This is known as a fretting resistance ( ).  A field of the order of  to  V/cm can breakdown this layer and this phenomenon is called A fretting.  Once the breakdown has taken place, the contact area around it enlarges, reducing the contact resistance.  This is called B fretting.


          Another process to maintain the integrity of the mating surface is to plate the ends with Tin, Nickel, or Silver.  The plated surfaces themselves tend to oxidize albeit at a lower rate.  It is advisable to cover the plated surface, immediately after plating, with the recommended covering material.  A protective compound still needs to be applied at the mating surfaces, before making a joint.  (Refer Section 4.4)      


4.3.2.4   Bolting Schedule


          There are no universal standards for the bolting schedule for busbar joints.  Most manufacturers follow the recommendations furnished in the handbook, produced by the association of Copper and Aluminium mills.  Many have in-house standards that have been generated and tested over a period.  Most   manufacturers follow any one of the two distinct practices detailed as under:


Bolting schedule (Figure – 4.12)


          The choice of the Bolting Schedule will depend upon the relative magnitude of the resistance to diversion (Rs ) and interphase resistance (Ri ).  A larger palm will result in an increase in weight of conductor material, number of fixings, plating area, and larger seal boots.  These can significantly increase the cost of the product, especially when the route length comprises several bolted joints.        



4.3.2.5   Joint Efficiency


          For a bolted joint having ‘n’ holes with diameter ‘d’, it can be established that the total Joint Resistance

                 

          The joint efficiency depends upon several factors and can exceed 1.0.  An ideal joint is one where the efficiency is close to 1.0 when the joint temperature is the same as that of the busbar.  (Since the surface area of the joint will be more than that of the busbar, it will offer more cooling area for convection and radiation.)


          Bi-metallic strips, if introduced between a Copper to an Aluminium joint to prevent Galvanic corrosion, will increase the interface resistance.



4.3.3   Clamping


          Clamping of conductors is extensively used in transmission lines and outdoor switchyards.  In the transmission lines, the conductors are received in drums.  The conductors are joined by Parallel Groove (PG) clamps and tap-off with T clamps.  The material is mostly Aluminium, to ensure compatibility with the material of the conductors.  When each phase has more than one conductor, spacer clamps are used to maintain the intra-phase spacing.  It also serves as a damper to prevent galloping and aeolian vibrations, helps withstand forces due to short circuit, and maintain electrical parameters.   In the switchyards, all the conductor joints and terminations are made with clamps & connectors.  Clamps & connectors manufacturing is a very specialized and mature industry.  The clamps and connectors installed in a switchyard are voltage specific, as they are tested for corona discharge. 


          Clamping has the advantage that the ends of the busbars do not need processing for jointing.  This allows a certain amount of flexibility that is needed in Switchyards where tolerances are large.


          When the clamp is of a different material from that of the conductor, it is susceptible to the formation of a Galvanic cell.


          Clamping is also universally adopted in the sandwich bus & low voltage cast resin bus, for jointing the conductors of the adjacent sections.





Continued..........

Comments

Popular Posts